Canada's elevator safety code is CSA B44, published jointly with ASME A17.1 as one binational document and adopted province by province. The 2019 edition (CSA B44:19) introduced the two-way messaging, text-display and in-car video requirement, Clause 2.27.1.1.3, for new installations and alterations as the authority having jurisdiction applies them. It is carried forward in the 2022 and 2025 editions.
A jurisdiction requires talk-and-text once it adopts B44:19 or later without excluding that clause. Nova Scotia adopted the 2019 edition but excluded the communication clauses, which is why adoption alone does not settle the question.
As of October 2026, 6 of 13 Canadian provinces and territories require talk-and-text emergency phones in elevators: Alberta, Manitoba, the Northwest Territories, Ontario, Québec and Yukon. 5 do not yet require them, and 2 are unconfirmed. Status was verified against each regulator's published adoption document. Download the full reference, with the map, as a PDF below.
Declared in force December 1, 2022 (Elevating Devices Codes Regulation). A 2023 Municipal Affairs notice announced B44:22, but it never came into force; a September 2025 notice confirmed B44:19 remains in force. B44:25 was published January 30, 2026 and is scheduled to come into force February 1, 2027 (Municipal Affairs notice, February 2026).
The Technical Safety Regulation adopts and enforces B44:19 without amendments, effective September 1, 2026 (Bulletin ITS 26-004, June 1, 2026).
Elevators and Lifts Regulations R-047-2024, s. 3(1)(a), in force July 15, 2024, adopt ASME A17.1/CSA B44-2019. Schedule A varies only 1.1.2(w), 1.1.2(x) and 1.1.3; Section 2.27 is untouched.
TSSA Code Adoption Document 295/22 adopts ASME A17.1-2019/CSA B44-19, in force August 1, 2022 (maintenance section 8.6 from January 1, 2023). No Ontario amendment to 2.27.1.1.
Construction Code, Chapter IV adopts the French edition of ASME A17.1-2019/CSA B44:19, in force July 13, 2024; the 12-month transition ended July 13, 2025. The RBQ's published list of main code changes adopted since the 2007 edition includes the elevator emergency communication system with video monitoring.
Fixed Conveyances Regulations, OIC 1998/040, s. 4.01 (added by OIC 2018/10): a listed code means the document "as amended or replaced from time to time," and a replacement takes effect on the later of six months after publication or the following April 1. B44:19 has applied since 2020 to 2021; B44:25 will by April 1, 2027.
B44:16 in force since April 30, 2020. Technical Safety BC consulted on B44:19 in 2023 and in 2026 says it is working with the Ministry toward a newer edition with no timeline set.
Regulation 2019-30 under the Elevators and Lifts Act defines the Code as ASME A17.1-2016/CSA B44-16.
The Chief Elevator Inspector's letter of December 14, 2021 adopted B44:19 for installations and alterations sold after December 31, 2021, but stated the 2019 emergency communication requirements "will not be a requirement in Nova Scotia"; emergency operation and signalling follow B44:16. The General Regulations cite CSA B44 "as amended from time to time" with no edition named, so confirm whether the exclusion carries forward.
Elevators and Lifts Act Regulations, s. 1(1)(e), define the Code as ASME A17.1-2013/CSA B44-13 (official consolidation current to December 26, 2015).
TSASK cites ASME A17.1-2013/CSA B44-2013; its FAQ describes the codes as proposed under the regulation rewrite. Confirm the edition in force with TSASK.
Amusement Rides and Elevating Devices Regulations, NLR 118/96 (under the Public Safety Act), s. 4(1)(a), cite "ASME A17.1/CSA B44" with no edition year. Confirm the enforced edition with Service NL before quoting.
The only published consolidation (Electrical Protection Regulations, inherited from the NWT) references CAN/CSA-B44-94. Confirm with the territorial authority.
Adopting B44:19 does not automatically mean every clause applies. Provinces can adopt an edition with variations that exclude specific sections, as Nova Scotia did for emergency signalling. Always confirm the clause, not just the edition. Where the code applies to an alteration, most authorities require only the altered component or system to meet the new edition (Manitoba says so explicitly), so whether a given modernization triggers 2.27.1.1.3 is a decision for the authority having jurisdiction.
For what the phone itself has to do, see our elevator emergency communication checklist. For the United States, see elevator phone requirements by state. Questions? Call (212) 732-4658 or email info@liftcomm.com.
Sources: TSSA Code Adoption Document 295/22; RBQ, Chapitre IV principales modifications and "Principales modifications du code ASME A17.1/CSA B44 adoptées par la RBQ depuis l'édition 2007"; Alberta Municipal Affairs, Elevator codes and standards page and notices of Oct 2023, Sept 2025 and Feb 2026; Manitoba Bulletin ITS 26-004; NWT Elevators and Lifts Regulations R-047-2024; Yukon Fixed Conveyances Regulations OIC 1998/040; Technical Safety BC; NB Reg 2014-147 as amended by 2019-30; PEI Elevators and Lifts Act Regulations; TSASK elevating devices page; NLR 118/96; Nova Scotia Chief Elevator Inspector letter, Dec 14, 2021, and Elevators and Lifts General Regulations. This reference is educational and is not a substitute for the code or a ruling from the authority having jurisdiction.